Description / Abstract:
This specification covers the minimum performance and material
requirements for resilient connectors used for connections between
precast reinforced concrete storm sewer structures conforming to
Specification C478 and pipes, and between precast reinforced
concrete pipe and laterals for storm drainage systems.
These connectors are designed to prevent soil migration between
the pipe and storm sewer structure, and between the pipe and
lateral.
The values stated in inch-pound units are to be regarded as
standard. The values given in parentheses are for information
only.
NOTE 1—This specification covers the design, material, and
performance of the resilient connection only. Connections covered
by this specification are adequate for hydrostatic pressures up to
6 psi (14 ft) without leakage when tested in accordance with
Section 7. Infiltration quantities for an installed system are
dependent upon many factors other than the connections between
storm sewer structures and pipe, and allowable quantities must be
covered by other specifications and suitable testing of the
installed pipeline and system.
The following precautionary caveat pertains only to the test
methods portion, Section 7, of this specification: This
standard does not purport to address all of the safety concerns, if
any, associated with its use. It is the responsibility of the user
of this standard to establish appropriate safety and health
practices and determine the applicability of regulatory limitations
prior to use. For a specific warning statement.