Description / Abstract:
The requirements of this code shall govern for the evaluation of
safety and serviceability of members in existing concrete
structures by load testing.
The requirements of this code shall apply to reinforced concrete
with prestressed reinforcement, nonprestressed reinforcement, or
both.
Procedures and requirements provided in this code are not
applicable to existing structures having concretes with compressive
strengths above 8000 psi unless permitted by the licensed design
professional.
For structures being erected under the requirements of a legally
adopted general building code, of which ACI 318-11 forms a part,
this standard shall not replace Chapter 20 of ACI 318-11.
Purpose
The purpose of this code is to establish the minimum
requirements for the test load magnitudes, load test procedures,
and acceptance criteria applied to existing concrete structures as
part of an evaluation of safety and serviceability to determine
whether an existing structure requires repair and rehabilitation,
to verify the adequacy of repair and rehabilitation measures
applied to an existing structure, or to provide for public health
and safety through structural safety and serviceability.
Load tests shall be conducted according to load test procedures
as described in Chapter 5.
All references in this code to the licensed design professional
shall be understood to mean persons who are licensed to practice
structural design in the jurisdiction where this code is being
used. The licensed design professional for a project is responsible
for and in charge of the evaluation of safety and
serviceability.